|
General Description |
Max
Poles |
Current &
Voltage Rating |
Max.
Interrupting
Capacity |
Approvals* |
ATR11


|
|
 |
1 |
|
|
 |
8 times normal rating for less than 6 amps |
 |
60 amps for greater than or equal to 6 amps |
|
|
ATR20


|
|
 |
1 |
|
 |
2.50 to 20 amps at 250Vac, 50/60Hz |
 |
2.50 to 20 amps at 50Vdc |
|
 |
Minimum 6 times normal rating for 250Vac |
 |
Minimim 4 times normal rating for 50Vdc |
|
|
SAR/SAS


|
|
 |
1 |
|
 |
15 amps at 125Vac, 250Vac, 32Vdc |
|
 |
500 amps |
|
|
SNAPAK©


|
|
 |
2 |
|
|
 |
1000 amps |
|
|
IPA

|
|
 |
3 |
|
 |
0.05-30 amps, 65Vdc |
 |
0.05-20 amps, 80Vdc (300 AIC) |
 |
0.05-25 amps, 250Vac, 50/60Hz |
 |
25.1-30 amps, 240Vac, 50/60Hz |
 |
0.10-15 amps, 250Vac, 400Hz |
 |
0.05-25 amps, 65Vdc (TUV) |
 |
0.05-25 amps, 250Vac, 50/60Hz (TUV) |
 |
0.05-15 amps, 250Vac, 400Hz (TUV) |
|
 |
1000 amps |
|
|
IAG/IUG/IEG/CEG
|
|
 |
6 |
|
|
 |
5000 amps, 240Vac, 50/60 Hz |
 |
1500 amps, 240Vac, 400 Hz |
 |
7500 amps, 80Vdc (IEG) |
 |
5000 amps, 80Vdc (CEG) |
 |
2000 amps, 250Vac, 50/60 Hz (VDE) |
 |
4000 amps, 80Vdc, (VDE) |
|
|
IAL/IUL/IEL
|
|
 |
6 |
|
 |
.050 to 100 amps, 65Vdc |
 |
.050 to 70 amps, 80Vdc |
 |
.050 - 70 amps, 240Vac, 50/60 Hz |
 |
.050 - 50 amps, 277Vac, 50/60 Hz |
 |
.050 - 50 amps, 277/480Vac, 50/60 Hz |
 |
.050 - 50 amps, 250Vac, 400 Hz |
|
 |
5000 amps, 240Vac, 50/60 Hz |
 |
1500 amps, 250Vac, 400 Hz |
 |
7500 amps, 80Vdc |
 |
2000 amps, 240Vac, 50/60 Hz (VDE) |
 |
2000 amps, 415Vac, 50/60 Hz (VDE) |
 |
4000 amps, 80Vdc (VDE) |
 |
1200 amps, 277/480Vac |
|
|
IAL/IUL/IEL

|
|
 |
3 |
|
|
|
|
IAL/IUL/IEL
|
|
 |
1 |
|
|
 |
10000 amps, 80Vdc |
 |
50000 amps, 65Vdc
(up to 150 amps) |
 |
10000 amps, 80Vdc
(>150 amps) |
|
 |
UL 489A Listed |
 |
CSA Certified |
|
IALR/IULR/IELR


|
 |
IELR versions meet IEC spacing requirements for installation in equipment that must comply with IEC 601 and 950, and VDE 0730, 0804, and 0805 |
 |
Designed to mount on standard 35mm DIN rails |
|
 |
4 |
|
|
 |
7500 amps, 80 Vdc |
 |
5000 amps, 250Vac, 50/60 Hz |
 |
2000 amps, 277Vac, 50/60 Hz |
 |
2000 amps, 250Vac, 50/60 Hz (VDE) |
 |
2000 amps, 415Vac, 50/60 Hz (VDE) |
 |
4000 amps, 80Vdc (VDE) |
|
|
209/219/229/279
|
|
 |
6 |
|
 |
.100 to 100 amps, 160Vdc |
 |
.100 to 100 amps, 125Vdc |
 |
.100 to 77 amps, 600Vac |
 |
.100 to 100 amps, 600Vac |
 |
.100 to 100 amps, 120, 240, 277, 480Vac |
 |
.100 to 100 amps, 125Vdc, 240Vac/415Vac (VDE) |
|
|
|
JAE/JRE/JLE

|
|
 |
6 |
|
|
|
|
AP/UP, AP/MIL

|
|
 |
3 |
|
AP Ratings |
 |
.050 to 20 amps, 240Vac, 50 Vdc |
UP Ratings |
 |
.050 to 20 amps, 50Vdc |
|
.050 to 15 amps, 120Vac |
|
.050 to 7.5 amps, 240Vac |
|
AP Ratings |
 |
500 amps, 50Vdc, 120Vac |
|
300 amps, 240 Vac |
UP Ratings |
 |
1000 amps, 50Vdc, 240Vac |
|
 |
QPL to MIL-PRF-39019 |
 |
UL Recognized (UP style only) |
|
APG/UPG, IPG
|
|
 |
4 |
|
 |
.020 to 30 amps, 277Vac |
 |
.020 to 30 amps, 250Vac, 65Vdc |
|
|
|
APL/UPL
205/295/205D
|
|
 |
9 |
|
|
|
|
*Consult factory for conditions of acceptability. |